Final Frequent Electrical Violations-(Residential)

 

Current adopted edition of National Electrical Code-2005

 

  1. Ladder not provided for inspection of attic equipment-. USBC 113.1.1
  2. Improper working space @ elec. panels and equip.-110.26
  3. Ground Fault requirements in kitchens, baths, garages, basement, outdoor, wet bar-210.8
  4. Recepts. within 6’ of laundry sink must be GFCI protected. 210.8 (a)(7)
  5. Bath recept. outlets not separate 20 amp circuit-210.11 (c) (3)
  6. “Combination Type” Arc Fault Circuit Interrupter requirements for all bedroom outlets, including lights, fans, smoke dets. etc. (210.12)
  7. Bath recept. outlet > than 36” from sink basin.-210.52 (d)
  8. Outdoor recept.outlet > than 6 1/2’ above grade. 210.52 (e)
  9. Recept. not located within 25’ of outdoor HVAC equip.-210.63
  10. Lights for interior stairs of 6 or more risers not switched at each level.-210.70 (a) (2) (c)
  11. Kitchen recept. located under countertop where overhang is > 6” beyond base.-210.52 (b) 5
  12. Kitchen countertop recept. spacing-210.52 (c)
  13. Concrete encased electrodes (rebar) if present, must be used as grounding electrode. 250.50 & 250.52(3)
  14. Bonding means for other systems not provided ie: phone/TV.-250.94
  15. Grounding electrode conductor not secured to bldg surface.-250.64 (b)
  16. Insulated Equip. ground # 6 and smaller must have entire length finished green.-250.119
  17. Grounded (neutral) conductors not isolated at sub-panels in same bldg.-250.142(b)
  18. PVC conduit installed where subject to damage not schedule 80.-300.5 (d)(4)
  19. Covers missing on outlet/junction boxes.-314.25
  20. Outlet boxes not flush with combustible surfaces.-314.20
  21. Switches not grounded.-404.9 (b)
  22. Circuit breakers installed > 6’ 7” above floor.-404.8
  23. Receptacles not mounted rigid to surface.-406.4(b)
  24. Wet location recept. covers not weatherproof with cord cap inserted.-406.8 (B)
  25. Receptacle located in tub space.-406.8 (c)
  26. Panel not labeled specifically.-408.4
  27. Ceiling fans, hanging fixtures located in 3’ x 8’ zone near tub/shower.-410.4 (d)
  28. Clothes closet light clearances.-410.8
  29. Cord length on appliances.-422.16 (b)
  30. Heat strip not identified on HVAC equip.-424.28
  31. Breaker lock/disconnect not provided for hard wired appliances ie: dishwasher, oven, water heater etc.-422.31(b)
  32. AC breaker/fuse size exceeds max. per label.-440.6
  33. Insufficient tub motor access.-680.73
  34. Tub motor not bonded to associated metal piping etc.-680.74
  35. Sign not posted at service indicating optional generator system on site.-702.8
  36. Holes in exterior of house not sealed at elec. penetrations.-IRC 703.1